Bookmark and Share

Ranges
    view more
    Related Categories
    view more
    advertisement

    DHW3-250 Heat Pump Water Heater Package

    Supplier verified July 2011 | listing #38995
    DHW3-250

    *AS/NZS 2712, 4234, and 5125 compliant. Independently tested and Low Temperature Class A certified.

    The DHW3-250 split water heating package. It incorporates a DHW7G01 heat pump which is specifically designed for directly heating potable water and a duplex stainless cylinder.

    DHW7G01
    Single Phase
    Current Load F.L.A. - (Amps) 4.4
    L x W x H (mm) 750 x 350 x 670
    Input – (kW) 1*
    Output – (kW) 3*
    Weight - (Kg) 55
    Air volume @ High Speed - (L/S) 600
    SPL@ 3m, low/high - (dB(A)) 42/44
    Minimum Water Flow Rate - (Litre/Sec) 0.3
    Refrigerant R407C
    Coil Epoxy Coated
    Fan Motor Multi-Speed
    Fan Propeller Direct Drive
    Pressure Switches High / Low
    De-ice Control Electronic Time / Temperature
    Water Temperature Operational Range 5°C — 63°C
    Ambient Operational Range -10°C — 50°C
    Min/Max Operational Pressures 2/10 bar
    *kW capacities vary depending on the conditions.

    250Ltr Custom SolarMax Duplex Stainless Steel Cylinder
    Suitable Heat Pump connections
    3kW Backup Element
    TPR Valve

    *water circulation pump must be adequately sized to ensure specified water flow requirements.